The instrument data for the Magnetic Flow Meter FE-2258, known at present, are shown in the table below:
|
Data Name
|
Data Set
|
Template ST-
|
| GENERAL |
|
Tag Number |
JF-B14-FE-2258 |
|
|
Service |
MP-B14-0002A/B MINIMUM FLOW BYPASS |
|
|
Line Number |
B14-RW-0008-4"-AC-HC1.0"E
|
|
|
P&ID/V&ID/MHD |
RD-M6-B14-M0001
|
|
|
Hazardous Area Class |
non-classified |
|
|
Agent Contamination Category |
D |
|
|
Ambient Temperature-Minimum |
40 oF
|
|
| Ambient Temperature-Maximum |
100 oF
|
|
| Supply Loss Failure Mode |
N/A |
|
|
Signal Loss Failure Mode |
N/A
|
|
| PIPELINE |
|
Line Size |
4 " |
|
| Line Schedule |
|
|
|
Pipe Material |
Hastelloy |
|
|
Pipe Insulation |
No (?) |
|
| PROCESS CONDITIONS |
|
Fluid Name |
Brine Conc. Feed |
|
|
Fluid Phase |
Liquid |
|
|
Corrosive |
Yes |
|
|
Erosive |
No |
|
|
Toxic |
No |
|
|
Build-up Tendency |
Yes |
|
|
PROCESS DESIGN CONDITIONS |
|
Design Pressure - Minimum |
|
|
| Design Pressure - Maximum |
150 psig |
|
| Design Temperature - Minimum |
|
|
|
Design Temperature - Maximum |
125 oF
|
|
| Liquid Conductivity - Minimum |
|
|
|
Liquid Conductivity - Maximum |
|
|
|
MATERIAL FLOW CONDITIONS |
| Flow Rate @ Minimum Flow |
65 AUS gal/min |
|
| Flow Rate @ Normal Flow |
216 AUS gal/min |
|
| Flow Rate @ Maximum Flow |
325 AUS gal/min |
|
|
Inlet Pressure @ Minimum Flow
|
50 psig |
|
|
Inlet Pressure @ Normal Flow
|
40 psig |
|
|
Inlet Pressure @ Maximum Flow
|
40 psig |
|
| Inlet Temperature @ Minimum Flow |
80 oF
|
|
| Inlet Temperature @ Normal Flow |
80 oF
|
|
| Inlet Temperature @ Maximum Flow |
80 oF
|
|
|
Density @ Minimum Flow
|
63.61 lb/ft3 |
|
|
Density @ Normal Flow
|
63.61 lb/ft3 |
|
|
Density @ Maximum Flow
|
63.61 lb/ft3 |
|
|
Viscosity @ Minimum Flow
|
0.85 cP |
|
|
Viscosity @ Normal Flow
|
0.85 cP |
|
|
Viscosity @ Maximum Flow
|
0.85 cP |
|
|
Pipe Line Velocity @ Minimum Flow
|
ft/s |
|
|
Pipe Line Velocity @ Normal Flow
|
ft/s |
|
|
Pipe Line Velocity @ Maximum Flow
|
ft/s |
|
| FLOWMETER BODY |
| Body Type |
Flanged std-form |
|
| Flow Tube Style |
|
|
| End Connection Size |
4 inch |
|
| End Connection Rating |
150 psig |
|
| End Connection Type |
Flanged |
|
| End Connection Rating |
RF |
|
| Flow Tube Diameter |
4 inch |
|
| Flow Tube Thickness |
|
|
| Hardware Mounting Kit |
N/A |
|
| Flow Tube Material |
stainless steel |
|
| Lining Material |
|
|
| End Termination Material |
stainless steel |
|
| Ground/Protective Ring Material |
|
|
| End to End |
|
|
| SENSING ELEMENT |
| Electrode Type |
|
|
| Insertion Length |
N/A |
|
| Electrode Material |
|
|
| COIL AND HOUSING |
| Housing Construction |
|
|
| Coil Connection Arrangement |
|
|
| Enclosure Type Number |
NEMA 4X |
|
| Signal Power Source |
|
|
| Signal Termination Type |
|
|
| Certification/Approval Type |
|
|
| Housing Material |
|
|
| TRANSMITTER BODY |
| Body/Flange Type |
|
|
| Process Connection Size |
|
|
| Process Connection Rating |
|
|
| Process Connection Type |
|
|
| Process Connection Style |
|
|
| Mounting Type |
|
|
| Body/Flange Material |
|
|
| Bolting Material |
|
|
| Gasket/O-ring Material |
|
|
| Mounting Kit Material |
|
|
| TRANSMITTER |
| Output Signal Type |
4-20 mA |
|
| Enclosure Type Number |
NEMA 4X |
|
| Electrical Connection Size |
|
|
| Electrical Connection Type |
|
|
| Digital Communication |
HART |
|
| Signal Power Source |
24 V(dc) |
|
| Integral Indicator Style |
LCD |
|
| Signal Termination Type |
|
|
| Certification/Approval Type |
|
|
| Enclosure Material |
|
|
| Write Protection |
|
|
| PERFORMANCE |
| Maximum Pressure at Temperature |
psig @ oF
|
|
| Working Temperature - Minimum |
psig @ oF
|
|
| Working Temperature - Maximum |
psig @ oF
|
|
| Velocity URL - Minimum |
ft/s |
|
| Velocity URL - Maximum |
ft/s |
|
| Maximum Sensor-Receiver Length |
N/A |
|
| Accuracy |
<= 0.5 % rate |
|
| ACCESSORIES |
| Connecting Cable Length |
N/A |
|
| PURCHASE |
| Purchase Order Number |
24852-MRA-JF08-J0001 |
|
| Item No. |
|
|