Instrument data in 

Control Systems Façade   latest update: 2007-02-02

Introduction

Below is a population of instrument data for the flow control loop shown on the P&ID snippet.

 

 

The instrument data for the Magnetic Flow Meter FE-2258, known at present, are shown in the table below:

 

Data Name

Data Set

Template ST-

GENERAL
Tag Number JF-B14-FE-2258  
Service MP-B14-0002A/B MINIMUM FLOW BYPASS  
Line Number

B14-RW-0008-4"-AC-HC1.0"E

 
P&ID/V&ID/MHD

RD-M6-B14-M0001

 
Hazardous Area Class non-classified  
Agent Contamination Category D  
Ambient Temperature-Minimum

40 oF

 
Ambient Temperature-Maximum

100 oF

 
Supply Loss Failure Mode N/A  
Signal Loss Failure Mode

N/A

 
PIPELINE
Line Size 4 "  
Line Schedule    
Pipe Material Hastelloy  
Pipe Insulation No (?)  
PROCESS CONDITIONS
Fluid Name Brine Conc. Feed  
Fluid Phase Liquid  
Corrosive Yes  
Erosive No  
Toxic No  
Build-up Tendency Yes  
PROCESS DESIGN CONDITIONS
Design Pressure - Minimum    
Design Pressure - Maximum 150 psig  
Design Temperature - Minimum    
Design Temperature - Maximum

125 oF

 
Liquid Conductivity - Minimum    
Liquid Conductivity - Maximum    
MATERIAL FLOW CONDITIONS
Flow Rate @ Minimum Flow 65 AUS gal/min  
Flow Rate @ Normal Flow 216 AUS gal/min  
Flow Rate @ Maximum Flow 325 AUS gal/min  

Inlet Pressure @ Minimum Flow

50 psig  

Inlet Pressure @ Normal Flow

40 psig  

Inlet Pressure @ Maximum Flow

40 psig  
Inlet Temperature @ Minimum Flow

80 oF

 
Inlet Temperature @ Normal Flow

80 oF

 
Inlet Temperature @ Maximum Flow

80 oF

 

Density @ Minimum Flow

63.61 lb/ft3  

Density @ Normal Flow

63.61 lb/ft3  

Density @ Maximum Flow

63.61 lb/ft3  

Viscosity @ Minimum Flow

0.85 cP  

Viscosity @ Normal Flow

0.85 cP  

Viscosity @ Maximum Flow

0.85 cP  

Pipe Line Velocity @ Minimum Flow

         ft/s  

Pipe Line Velocity @ Normal Flow

         ft/s  

Pipe Line Velocity @ Maximum Flow

         ft/s  
FLOWMETER BODY
Body Type Flanged std-form  
Flow Tube Style    
End Connection Size 4 inch  
End Connection Rating 150 psig  
End Connection Type Flanged  
End Connection Rating RF  
Flow Tube Diameter 4 inch  
Flow Tube Thickness    
Hardware Mounting Kit N/A  
Flow Tube Material stainless steel  
Lining Material    
End Termination Material stainless steel  
Ground/Protective Ring Material    
End to End    
SENSING ELEMENT
Electrode Type    
Insertion Length N/A  
Electrode Material    
COIL AND HOUSING
Housing Construction    
Coil Connection Arrangement    
Enclosure Type Number NEMA 4X  
Signal Power Source    
Signal Termination Type    
Certification/Approval Type    
Housing Material    
TRANSMITTER BODY
Body/Flange Type    
Process Connection Size    
Process Connection Rating    
Process Connection Type    
Process Connection Style    
Mounting Type    
Body/Flange Material    
Bolting Material    
Gasket/O-ring Material    
Mounting Kit Material    
TRANSMITTER
Output Signal Type 4-20 mA  
Enclosure Type Number NEMA 4X  
Electrical Connection Size    
Electrical Connection Type    
Digital Communication HART  
Signal Power Source 24 V(dc)  
Integral Indicator Style LCD  
Signal Termination Type    
Certification/Approval Type    
Enclosure Material    
Write Protection    
PERFORMANCE
Maximum Pressure at Temperature

              psig @          oF

 
Working Temperature - Minimum

              psig @          oF

 
Working Temperature - Maximum

              psig @          oF

 
Velocity URL - Minimum          ft/s  
Velocity URL - Maximum          ft/s  
Maximum Sensor-Receiver Length N/A  
Accuracy <= 0.5 % rate  
ACCESSORIES
Connecting Cable Length N/A  
PURCHASE
Purchase Order Number 24852-MRA-JF08-J0001  
Item No.  

 

 

RDF Listing